Why SIN-11?

Get our full range of cloud offering in the SIN-11 data center, a highly secured carrier neutral facility and part of the Pacnet Enabled Network (PEN). In this data center, we offer connections to the Equinix Internet Exchange and SG-IX.

Products in this location

Colocation
Facility
Connectivity
Power
Fire Protection
Security
Certifications

Location details

facility

Facility

  • Gross Floor Area: 155,000 sq ft (14,400 m2)
  • Gross White Space: 45,000 sq ft (4,180 m2)
  • Total colocation racks capacity: 1500
  • 4,200 mm floor to ceiling height
  • 800 mm raised floor height
  • Floor loading: 10kN/sqm
  • Earthing and lightning protection systems installed
  • All critical infrastructure and customer impacting infrastructure located on raised floor beds
  • High efficiency water-cooled chillers with N+1 redundancy
  • Thermal storage tanks for uninterruptable cooling
  • Dual, diverse chilled water risers
  • Cooling density up to 1.5kW/sqm in data centre
  • 20-25°C temperature
  • 50% +/- 20% relative humidity
  • N+20% CRACs
  • Racks deployed in 8-tile hot/ cold aisle
connectivity

Connectivity

Carriers:

  • NTT
  • PCCW
  • Tata GTT
  • Cogent
  • Telia Carrier
  • Vodafone
  • Telstra
Power

Power

  • 12 MVA Utility supply
  • Dual source power from power source to each rack (dual bus topology) with no common point of failure
  • N+1 distributed UPS (6,000 kVA)
  • 2 kVA standard power up to 6 kVA
  • 2N Power distribution to IT racks
  • 60,000 liters fuel capacity; equivalent to 24 hours run-time at full load
  • Fuel refill within 4 hours of activation
  • 10 minutes battery autonomy
  • N+2 diesel generator redundancy
  • 2N power distribution to IT racks
  • 2 x 32A CEEFORM power sockets per rack
  • 2 x AP8853 intelligent power strips per rack
Fire suppression

Fire Suppression

  • 24×7 decentralized monitoring of M&E plant room & redundant systems
  • Gaseous fire suppression and dry-pipe pre-action sprinklers
  • Very Early Smoke Detection Apparatus (VESDA)
  • Sub-raised floor water detection system installed around CRAC units and along perimeter of room
  • FM200 fire suppression
  • Doors and partitions minimally 2-hours rated
Security

Security

  • External Perimeter fence with 24 x7 CCTV monitoring and guard patrols
  • Footage stored for 30 days
  • Man traps to data hall
  • 2 factor authentication (biometric/ card)
  • Pre- authorized visitors only
  • Visitor logs are kept for one year